
5. If an additional wired Magnetic Contact is
required, this should be wired to the terminal
block provided in the battery compartment and
the jumper link (S2) below should be removed.
The wired contact should be connected using two
core (24AWG) wire of maximum length 1.5m.
A cable entry cut-out is provided beside the
terminal block in the battery cover.
6. Set the Detector as described in the next section.
7. Slide the batteries supplied into the holder,
ensuring that the positive (+) side is uppermost on
each battery as it is installed.
8. Carefully refit the battery holder onto the Detector
ensuring that the spring connectors slide onto
either side of the circuit board.
9. Refit the battery cover.
Setting the Magnetic
Contact Detector
1. Located in the battery compartment is a row of 11
DIP switches.
2. DIP switches 1-8 are used to set the House Code
for the Detector and must be set to the same
ON/OFF combination as the House Code DIP
switches in all other system devices.
3. DIP switches 9-11 must be set as follows.
4. If additional external contacts are wired to the
Detector, remove the jumper link S2 on the PCB.
I
mportant: If external contacts are not connected
t
hen jumper link SW2 must be fitted for the
D
etector to operate correctly.
Testing the Magnetic
Contact Detector
Ensure that the system is in Test/Service Mode
1. Remove the battery cover from the Detector.
As the battery cover is removed the LED on the
Detector will illuminate for approx. 1 second to
indicate that the tamper switch has been
activated.
2. Open the door/window. As the Magnet is moved
away from the Detector the LED will illuminate for
approx. 1 second to indicate that the Detector has
been triggered.
3. If connected, operate the wired Magnetic Contact.
As the contact is opened the LED on the Detector
should illuminate for 1 second to indicate that it
has been triggered.
4. Replace the battery cover on the Detector.
5. It is recommended that the operation of the
Detector is also tested with the alarm in normal
operating mode to ensure that the Detector will
successfully trigger a Full Alarm condition.
14
Detector
Magnet
Cut-out for
C
able Entry
Battery Cover
Alternative
Mounting
(Ensure
back
surfaces
are flush)
ON
ECE
1 2 3 4 5 6 7 8 9 10 11 12
8mm
11mm
Terminal Block for Additional Wired
Magnetic Contact Detector T1
Anti-Tamper
Switch SW2
Location of
Key-hole Screw
(underside)
Jumper
Link S2
Hole for
Mounting
Screw
Batteries
x 2
ON
1 2 3 4 5 6 7 8 9 10 11 12
Zone
House Code
ECE
Dip Switch
12 Not Used
DIP 9
ON
DIP 10
ON
DIP 11
OFF
Comentarios a estos manuales